Recent studies suggest
both fire-rated glazing and sprinkler systems are necessary to provide the necessary
protection against fire in new construction projects.
The relationship between glass and sprinkler systems is unique. Understanding how the
two work together is critical for deciding whether to install fire-rated glass, or
non-rated products such as tempered or heat-strengthened glass. Ultimately, the choices
that are made can affect life safety drastically.
Currently, some building codes allow what are known as trade-offs. With a trade-off, an
architect can circumvent fire-rating requirements by specifying sprinklers instead of
traditional fire-rated building materials, including glass. The assumption is that
tempered glass with sprinklers will provide an equivalent level of fire protection to
fire-rated glass. However, a number of tests have been performed over the past two decades
to determine how sprinkler systems and window glass interact during a fire. The results
have shown that relying strictly on sprinklers for fire safety may be a dangerous choice.
Are Sprinklers Infallible?
Because sprinkler systems have been so effective in reducing fire fatalities and property
damage, it is often taken for granted that they work 100 percent of the time.
Classified as active protection systems, sprinklers require a sequence of events to occur
in order for them to activate properly. So even when they are mechanically sound,
sprinklers are still subject to various forms of human error. There have been numerous
incidents recorded where something interfered with that activation process and the
sprinklers did not perform as needed.
Usually these problems have been due to improper maintenance of the sprinkler system. For
example, tenants have accidentally painted over sprinkler heads. Water supply valves have
been shut off, and water pressure has sometimes been inadequate to support the sprinklers.
These are all preventable, yet at the same time they represent the unknown factor that is
always present when systems are dependent upon people.
Occasionally, difficulties with sprinklers arise during the fire itselfin spite of
good maintenance. In some cases a fire has overwhelmed and melted nonmetallic piping for
sprinklers. Other times, firefighters have diverted water to their trucks too soon,
leaving sprinkler systems with no supply.
The point is simply that installing a sprinkler system does not guarantee performance when
it is needed. While complications may be the exception rather than the rule, any number of
factors can inhibit the way sprinklers function in a real life emergency.
When sprinklers fail to suppress a fire, for any reason, other means of protection are
needed to keep the flames and deadly smoke from spreading to other areas of a building.
Fire-rated materials such as glass, doors, walls and ceilings are designed to act as fire
barriers around the clockwhether or not the sprinklers are functioning. If those
passive protection elements have been eliminated from the plans in lieu of sprinklers,
then there is no failsafe when a breakdown occurs in the sprinkler system.
Glass and Sprinklers
What if the sprinkler system does work properly? If sprinklers seem to be reliable the
majority of the time, what can be expected in terms of glass performance?
It is no secret that most glass does not do well in fire conditions. Typical window glass
will break at 250 F, and tempered glass will only last until about 500 F. When
temperatures soar beyond that (as is typical within the first five minutes of a fire),
different products are required. Fire-rated glass products (such as ceramics, wired glass,
transparent firewalls, etc.) have been furnace tested in excess of 1,600 F, and they are
still able to remain in the frame and provide protection.
When you add sprinklers to the mix, the situation becomes more complicated. On the one
hand, sprinklers do have a cooling effect. In theory, glass of any kind kept adequately
cool should be able to survive a fire indefinitely. On the other hand, if water from
sprinklers impacts non-rated glass that is already hot, the water creates thermal stresses
in the glass that cause it to shatter. This means sprinklers can actually cause more harm
than good if used in combination with the wrong type of glass.
Many types of fire-rated glass are on the market today that are compatible with
sprinklers, regardless of glass temperature. To achieve a rating of 45 minutes or greater,
it is mandatory (according to UBC 7-2, UBC 7-4, ASTM E-163, NFPA 252,NFPA 257, UL 9 and UL
10B) for any glazing material to endure a hose stream test immediately after the fire
test. The hot glass and framing system is removed from the test furnace and blasted with
water from a fire hose. The glass does not receive a passing grade if it falls out of the
frame. As a result, fire-rated glass is well prepared to handle water from sprinklers,
fire extinguishers, or other sources.
In spite of this fact, some people have pushed alternatives that would allow the use of
non-rated glass in fire-rated areas. Manufacturers have developed special window sprinkler
systems designed to activate early and bathe the entire glass surface with water.
Independent laboratories such as UL have tested such systems in combination with tempered
glass. Their test results have shown that when fires start several feet away from the
glass and sprinklers come on quickly, tempered glass is able to remain intact. However, if
a fire starts close to the glass surface, it can create enough heat to break the glass
before the sprinklers activate. Or, as mentioned above, if the glass gets hot and then the
water hits it, the glass will shatter and fall out of the frame.
To compensate for this, some manufacturers recommend a 36-inch high ponywall to keep
flammable objects away from the glass, reducing the potential for fires close to the glass
surface. Yet ponywalls often turn into convenient storage areas for papers, picture
frames, etc. Those items can easily ignite and negate the value of the ponywall.
If anything, this glass performance issue becomes more critical the better the sprinklers
are working. Sprinklered fires generate tremendous amounts of smoke, since they usually
continue to smolder for some time. Smoke inhalation is by far the leading cause of deaths
in a fire. If windows have been blown out because of the sprinklers, smoke will spread
throughout the building, threatening more lives.
If sprinklers are nearby, it is best to install fire-rated glass that can pass the hose
stream test. This provides the greatest level of safety and ensures fire-protection that
is independent from the sprinkler system. The stakes are too high to settle for products
that only work under certain conditions.
Jerry Razwick is president of Technical Glass Products, based in Kirkland, Wash.
USG