Code Conflicts: Navigating Force Requirements in Door Hardware
Codes are confusing. What one state enforces, another lacks, leading to compliance issues and costly hardware replacements. Building codes set minimum requirements for designing and constructing structural systems and other aspects of commercial and residential buildings.
In the United States, building codes are administered mainly by state and local governments. For instance, while California’s codes focus more on earthquakes, Florida’s include more measures addressing hurricanes. Some states may limit or strike out new requirements they view as too costly or unnecessary, while others may see value in the updates.
States also have different accessibility standards, such as the California Building Code, Texas Accessibility Standards and the Code of Massachusetts Regulations, all impacting the type of door hardware installed.
The confounding nature of building codes and the various accessibility standards has forced some companies to replace newly installed panic hardware that did not meet force requirements. This issue was raised at Glass TEXpo™ ’25 in San Antonio during a presentation by Doug DeRusha, Frameless Hardware Company’s (FHC) vice president of sales.
During the presentation, DeRusha noted that one source of confusion is the requirement in some standards regulating door hardware to operate with five pounds of force or less. This requirement contradicts other codes that require panic hardware and door latches to operate with 15 pounds of force or less.
Conflicting Standards
Lori Greene, manager of codes and resources at Allegion, explains that the adopted building code in most states references an accessibility standard called International Code Council (ICC) A117.1. The 2017 edition of this standard and the 2021 and 2024 editions of the International Building Code (IBC) include limitations on the operable force for hardware.
“Before these editions, the force to unlatch the door was not explicitly addressed in A117.1, but the IBC stated that doors had to unlatch with 15 pounds of force or less,” notes Greene. “The current limits in these codes for the operable force of hardware are 15 pounds of pushing/pulling motion, such as panic hardware, and 28 inch-pounds of rotational motion, such as a lever handle.”
However, some states reference the Americans with Disabilities Act (ADA) standards in their building codes instead of ICC A117.1. California’s code, for instance, includes a five-pound force requirement instead of 15 pounds.
“In states that use the ADA standards, the five-pound limit is often enforced during design and construction, but in other states, it may not be implemented until years later,” explains Greene. “Often, it is never enforced. This has to do with how the ADA is enforced nationwide—it typically involves complaints from users, not enforcement by code officials (except where the ADA is adopted as the state standard).”
Greene says the confusion about the force requirements centers around an editorial change to the ADA standards. However, when the standards are updated, the industry will attempt to align ADA and A117.1.
“I think this will be successful because U.S. Access Board representatives did not object to the 15-pound/28-inch-pound change in the IBC and A117.1,” she adds. “The problem is that it has been 15 years since the editorial change was made, and we have not had an opportunity to fix it.”
Greene says that in states referencing the ADA instead of A117.1 during design and construction, code officials could flag hardware with a higher operable force during site inspections. In other states, it’s possible that someone could file an ADA complaint about the hardware’s operability at any time during the building’s life, but this has not been a common occurrence.
“[Building code institutions] come out with these code updates, and they’re not adopted by building code inspectors in the state,” he explains. “That’s what’s happening in California. The force-requirement standards have been in the codes, but they’ve never been enforced. Nobody has made products to satisfy it. Suddenly, in the last year, it’s popped up in California, and now other states will likely start enforcing it.”
Daniels says the issue is that companies will develop a product to meet the code and advertise it to meet current requirements, and now everyone is rushing to meet the code. In that rush, companies ignore the fact that while the door must open with five pounds of pressure, the handle must also.
“Even if the door opens with five pounds of pressure, the handle has to have a separate test that requires it to open with five pounds of pressure,” he says. “That’s how those people get caught. They have an ADA door that’s been used for 20 years, meets all the codes, but are now being told that the handles don’t meet the codes.”
This is a big problem for builders and installers. Many buildings have five-pound closers that can’t keep the door closed due to the pressure inside, which will blow the door open several inches. There are adjustable closers, but Daniels jokes that those are only made to be adjusted out of specification.
Jokes aside, Daniels says the consequences for installing doors that don’t meet force requirements can be costly.
“The consequences are that you must replace the hardware or the door to meet the codes,” he says. “The big thing is to make people aware that they need to check with their jurisdiction to make sure what they’re putting in meets code and to check with their manufacturer to ensure they have the right product.”
Joshua Huff is the senior editor of USGlass magazine. Email him at jhuff@glass.com and connect with him on LinkedIn.